Gas Pipeline


Project name

Location

Country

Market area

 

Gas Pipeline

West Midlands

UK

Utilities

 

Requirement

Despite the well insulated and aluminium clad section of the PRS pipeline, significant corrosion was detected on the outer surface of the inner pipe, caused by surface condensation due to low gas temperatures and humid conditions in a highly aggressive environment. The above ground gas pipe (steel) required coating to prevent further corrosion of pipes, valves and flange bolts while remaining in service. An expected life of 10 years before first maintenance was also required. The Corroless™ system was recommended to meet these requirements.

Preparation

The pipes were hydrojetted and manually prepared to St2 standard of EN ISO 8501-1:2007 and then hydrojetted again to remove any further dust and contamination.

Coatings

The pipes  were patched prime with Corroless™ EPF followed by two full coats of Corroless™ EPF.

Product (per coat)

DFT (per coat)

Colour

Corroless™ EPF

200 microns
patch prime

Black

Corroless™ EPF

200 microns

Buff

Corroless™ EPF

200 microns

Black

 

Comments: 
This work was carried out and inspected 11 years later and was found to be in very good condition, with no further inspection intended for a further 4 to 5 years. The previous system had lasted for only 7 years.